Sheet M-104
HVACconcept
Dual-duct HVAC system: how mixing boxes work and why it is rarely specified
One-line orientation
A dual-duct system runs separate hot and cold air mains to every zone and blends them at a mixing box — powerful temperature flexibility, but the simultaneous heating-and-cooling waste makes it rare in new construction.
Key points
- Two supply ducts: the central AHU conditions two separate air streams — one heated and one cooled — and delivers both through parallel duct mains to every zone in the building.
- Mixing box: at each zone a mixing box (also called a mixing terminal unit) blends the two streams. The zone thermostat modulates dampers in the mixing box to proportion hot vs cold air to hit the setpoint. More cold air = cooling; more hot air = heating.
- Thermostats: each zone has its own thermostat that independently controls its mixing box dampers — giving precise per-zone temperature control.
- Applications: historically used in hospitals, large laboratories, and complex office buildings requiring flexible simultaneous heating and cooling across many zones.
- Energy tradeoff:
- A classic constant-volume dual-duct system maintains hot and cold air streams and mixes them at each zone. Variable-volume dual-duct versions also exist.
- At every mixing box, the final supply temperature is achieved by partially canceling out energy already spent on heating and on cooling — similar to VAV reheat but potentially at larger scale.
- Dual-duct systems are recognized as high-energy-use systems.
- Space requirement: dual-duct systems require substantially more duct space than comparable single-duct systems. Do not memorize an exact multiplier.
- Why rarely specified today: VAV with terminal reheat offers similar per-zone precision at lower duct space cost; energy codes have become more restrictive; first cost and maintenance complexity are high.
Confusions / comparison
| Standard VAV | VAV with reheat | Dual-duct | |
|---|---|---|---|
| Supply ducts | 1 (cool) | 1 (cool) | 2 (hot + cold) |
| Terminal unit | Damper only | Damper + heating coil | Mixing box (two dampers) |
| Per-zone heat + cool | Cooling only | Yes — reheat coil | Yes — mixing box |
| Energy efficiency | High | Moderate | Low — continuous H+C |
| Duct space | Standard | Standard | ~2× duct volume |
| Use today | Common | Common (hospitals, labs) | Rare (legacy / retrofit) |